Behavior of Adjacent Structures under Pounding Forces

Antony Mohsen Kamal Massoud;

Abstract


This thesis presents an analytical study of the behavior adjacent buildings with different configurations, having non-sufficient separation distance to avoid their impact, when subjected to seismic loads. The research work was done by applying four ground motion records normalized to PGA = 0.25g in a non-linear time history analysis.
First the selected software (CSI ETABS) was verified, regarding it’s time history analysis and the implemented link element (gap element) that has only compression stiffness. Verification is done by numerical comparison between software results and numerical time stepping procedure (using Excel Spreadsheets) for different single degree of freedom (SDOF) and multi-degree of freedom systems under dynamic loads.
The first case was a heavy (stiff) building adjacent to a light (less stiff) one. This case has been modeled three times in a 2D model, replicated frame elements model with no slabs, and (frame + slab) elements model. The three models were tuned to have same fundamental period, then compared in order to be evaluated. It was concluded that the three models have responded similarly to pounding. A sensitivity study is done next for the gap element stiffness used. In-fill walls inertia were added and their effects on displacements and pounding behavior were studied. The gap element distribution was changed in order to study its effects on pounding behavior (in case of no torsional moments). The effect of mass and stiffness and damping of each building on pounding forces is studied for each variable in each building. The code separation distance (SRSS) was assessed for different records.
The second case was a 4-story (stiff) building adjacent to a 7-story (less stiff) one, maximum lateral displacements for each building in approach and restitution phases were plotted, as well as displacement time history, story acceleration time history and pounding force time history for different separation distances. In addition to comparing columns maximum bending moments in each direction, for no pounding and pounding with different separation distances cases. It was concluded that the 7-story building responses were significantly affected by pounding more than the 4-story building, especially in the restitution phase.


Other data

Title Behavior of Adjacent Structures under Pounding Forces
Other Titles سلوك المبانى المتجاورة تحت تأثير أحمال الطرق
Authors Antony Mohsen Kamal Massoud
Issue Date 2015