A microturbine interface system with LVRT capability

Hamouda, Mohamed R.; Mostafa Ibrahim Mohamed Marei; Badr, Mohamed A.;

Abstract


Microturbine Units (MTU) are used widely as distributed generators for their proved advantages. This paper presents an interface system for the Microturbine Unit (MTU) based on back-to-back converter to operate in grid connected and islanding modes. Besides regulating the active power fed from the MTU, during the grid-connected mode, the proposed interface system regulates the Point of Common Coupling (PCC) voltage at its rated value. Moreover, the proposed interface system is controlled to have a Low Voltage Ride-Through (LVRT) capability by feeding the grid with reactive power during grid faults. Furthermore, the proposed interface system keeps the voltage and frequency at the load terminal during the islanding mode of operation with the same control structure. Simulation results are provided to evaluate the dynamic performance of the proposed MTU interface system at the different modes of operation.


Other data

Title A microturbine interface system with LVRT capability
Authors Hamouda, Mohamed R.; Mostafa Ibrahim Mohamed Marei ; Badr, Mohamed A.
Keywords Grid-connected;islanding | LVRT;microturbine;Voltage regulation
Issue Date 28-Sep-2014
Conference 2014 Australasian Universities Power Engineering Conference, AUPEC 2014 - Proceedings
ISBN 9780646923758
DOI 10.1109/AUPEC.2014.6966646
Scopus ID 2-s2.0-84929441590

Recommend this item

Similar Items from Core Recommender Database

Google ScholarTM

Check

Citations 2 in scopus


Items in Ain Shams Scholar are protected by copyright, with all rights reserved, unless otherwise indicated.