Coordination of the Synchronous Generator Protection with Generator Capability Charts
WAEL HAMDY MAHMOUD YOUSEF;
Abstract
The large generating units are one of the important components in
producing electric power to the power system. Therefore, it requires
highly reliable protection relays to minimize the possibility of damage
occurring under fault conditions. There are varieties of protective relays
to provide secure and reliable protection for Synchronous Generators
(SG) and Generator Step-Up Transformer (GSUT). The differential
protection is a reliable method of protecting generators, transformers,
large motors, buses, cables and transmission lines from the effects of
internal faults. The main benefits of this protection type are isolating the
faulty unit accurately and fast. The generator-transformer unit overall
differential protection relay (87O) is designed to be a backup protection
for SG, GSUT, and Unit Auxiliary Transformer (UAT) differential
protection systems. The setting of the relay (87O) usually coordinated
with differential protection for SG, GSUT, and UAT by a time delay,
Pickup current, and/or slope of restrained curve to avoid mal-operation
during normal operating conditions
producing electric power to the power system. Therefore, it requires
highly reliable protection relays to minimize the possibility of damage
occurring under fault conditions. There are varieties of protective relays
to provide secure and reliable protection for Synchronous Generators
(SG) and Generator Step-Up Transformer (GSUT). The differential
protection is a reliable method of protecting generators, transformers,
large motors, buses, cables and transmission lines from the effects of
internal faults. The main benefits of this protection type are isolating the
faulty unit accurately and fast. The generator-transformer unit overall
differential protection relay (87O) is designed to be a backup protection
for SG, GSUT, and Unit Auxiliary Transformer (UAT) differential
protection systems. The setting of the relay (87O) usually coordinated
with differential protection for SG, GSUT, and UAT by a time delay,
Pickup current, and/or slope of restrained curve to avoid mal-operation
during normal operating conditions
Other data
| Title | Coordination of the Synchronous Generator Protection with Generator Capability Charts | Other Titles | التنسيق بين وقاية المولدات المتزامنة وخرائط التشغيل المنتظم لهذه المولدات | Authors | WAEL HAMDY MAHMOUD YOUSEF | Issue Date | 2018 |