Ultra high speed relaying approach for six-phase transmission lines
Mansour, M.M.; Hossam E.A. Talaat; Hajjar, Ammar A.;
Abstract
This paper introduces a traveling wave-based relaying approach dedicated to sophisticated protection of six-phase transmission lines. In this ultra-high-speed (UHS) approach fault detection classification, and faulted phase selection can be achieved within a quarter of cycle. Two discriminants are used to differentiate between transients due to faults in the protected zone from other transients or faults occurring outside the protected zone.
Other data
| Title | Ultra high speed relaying approach for six-phase transmission lines | Authors | Mansour, M.M. ; Hossam E.A. Talaat ; Hajjar, Ammar A. | Keywords | Fault classification;Phase selection;Six-phase transmission lines;Traveling waves;UHS relaying | Issue Date | 1-Jan-2002 | Journal | IEEE Power Engineering Review | ISSN | 02721724 | DOI | 10.1109/MPER.2002.1029977 | Scopus ID | 2-s2.0-0036710267 |